Ravel Release Station
ravel-re-716p1tlp-g-release-pull-station-green-main-ksa
ravel-re-716p1tlp-g-ul-listed-signaling-mark-ksa
ravel-re-716p1tlp-g-technical-specification-ksa

Click on the image to enlarge it

RAVEL

Click here for more RAVEL
Lift & Pull — SPST

Ravel RE-716P1TLP(G) Manual Release Station — The Manual Discharge Button in a Painted Die-Cast Housing with a 10 Amp SPST Switch

Overview

  • Every gas suppression system has three manual stations in three different colours, and each colour does a job the others do not: red to raise the alarm, yellow to abort or delay the discharge, and green — this item — to start the discharge by hand. The Ravel RE-716P1TLP(G) is the button an operator reaches for on seeing the fire itself, rather than waiting for the automatic detection sequence to complete, and it initiates the discharge of gas or clean agent through the connected control panel. Because operating it leads to a real discharge, it is built around a dual-action lift then pull movement that no passing touch or accidental brush can carry out, and it can be reinforced with a break glass rod that makes operation a deliberate act and leaves a visible trace of any use — or left without one where faster access matters more, with replacement of the rod requiring no special tools so the station is back in service straight away. This is also a device that may sit untouched for years and then be required to work first time, which is the lens to read its construction through: the enclosure is non-toxic die-cast alloy with smooth edges and a low profile that does not obstruct movement in a corridor, behind it sits a black 14 Ga steel plate that takes the strain of wall fixing, and every component is either prepainted or carries a treated surface so that slow corrosion over the years does not become the reason for failure at the decisive moment — a real consideration in Eastern Province humidity and industrial site conditions. The cover is secured by a hex screw or a key lock, so the enclosure opens only to an authorised hand. On the wiring side the station is not a source of voltage but a dry contact: a snap action SPST switch that opens or closes a path, and its rating of 10 amps at 120 VAC is the ceiling of its capacity, not a condition of its use, while the circuit voltage and current come from the control panel to which the station is wired through a two-position terminal block on a standard single-gang box. The compatible Ravel panels are the RE-120GR for gas release and the RE-25AR for agent release. The station is UL Listed — Signaling, it weighs 15.5 oz, and its origin is India. Available from Al-Najma Al-Wataniyah Est. with a quality guarantee and fast supply to projects across the Kingdom in Riyadh, Dammam and all regions.

Technical Specifications

SpecificationValue
CategoryFire Alarm & Gas Release Systems — Manual Release Station
BrandRavel
ModelRE-716P1TLP(G)
FunctionManually initiating the discharge of gas or clean agent
Operating MechanismDual action — lift then pull
Break Glass RodAvailable — the station works with or without it, and replacement requires no special tools
HousingPainted non-toxic die-cast alloy, low-profile design with smooth edges
Back Plate14 Ga plated steel, black
Surface TreatmentAll components prepainted or with plated surfaces to inhibit corrosion
AccessHex screw or key lock
SwitchSnap action, SPST
Electrical Rating10 A at 120 VAC (maximum contact capacity)
Terminal BlockTwo position
MountingSingle gang
Width3.200 in (approx. 81 mm)
Length4.750 in (approx. 121 mm)
Depth0.875 in (approx. 22 mm)
Weight15.5 oz
ColourGreen
CertificationUL Listed — Signaling
Compatible PanelsRE-120GR (conventional gas release panel) · RE-25AR (conventional agent release panel)
Country of ManufactureIndia
SKURE-716P1TLP(G)

Size & Color Table

Article CodeColourSize
RE-716P1TLP(G)GreenSingle model — single-gang mounting

Documentation & Standards

  • This station is UL Listed under the Signaling category for signalling devices in fire systems. The table below translates each line of its specification into practical terms, to support matching it against the panel drawing before purchase:
  • Additional reference standards for the Saudi market:
  • NFPA 2001 (Clean Agent Fire Extinguishing Systems — and the reference for manual actuation requirements within them)
  • NFPA 72 (National Fire Alarm and Signaling Code — the reference for the design and installation of manual actuation devices)
  • UL 38 (the American standard for manually actuated signaling boxes)
  • Saudi Civil Defence (the authority for approving gas suppression systems and their accessories in the Kingdom)
ItemWhat It Means in Practice
UL Listed — SignalingUnderwriters Laboratories listing under the signalling device category, which is what project specifications and approval files require of fire system devices
SPST switchSingle pole, single throw — one contact changes state on operation, matched against the manual release input at the panel
10 A at 120 VACThe maximum contact capacity — the station works as a dry contact whose operating voltage is set by the connected system
Snap action switchA decisive rather than gradual transfer between the two states, so no chattering signal arises on a slow pull — which matters directly on an item that initiates a discharge
Lift then pull mechanismTwo deliberate successive movements that prevent a discharge being started by a single accidental touch
Break glass rodAn optional physical barrier that makes operation a deliberate act and leaves a visible trace of any use

Industrial Applications

  • B2B sectors — detailed engineering use:
Sector / ApplicationEngineering Use Detail
Clean agent suppression systemsThe item that allows discharge to be started by hand on sight of fire, without waiting for the automatic detection sequence to complete
High-value goods warehousesLocations where the difference of seconds between starting the discharge and waiting for detection is a difference in the size of the loss
Server rooms and data centresEnclosed environments staffed by technicians familiar with the system who are able to take the discharge decision themselves
Transformer and main switchboard roomsLocations with a high heat load where a visible manual means of initiation is preferred
Coastal and industrial facilities in the KingdomPrepainted components and corrosion-inhibited surfaces suit humid and salt-laden conditions
Refurbishment and device replacement projectsMounting on a standard single-gang box makes replacement in an existing installation straightforward

Supply Information

FieldValue
Lead Time2-3 Business Days
CoverageRiyadh · Dammam · Jeddah · Jubail · Yanbu · and all regions
Project SupplyAvailable — contact the sales team to price the release and abort stations together and review the bill of quantities against the control panels

Frequently Asked Questions

Q1: What is the difference between the green, yellow and red stations?

  • Three functions in three colours: red is an alarm initiating device, yellow is the station that aborts or delays the discharge, and green — this item — is the station that starts the discharge by hand. A complete system needs the green and the yellow together: one to begin the discharge and one to stop it. The item is always matched against the system drawing and its bill of quantities before purchase.

Q2: What prevents it being operated by mistake?

  • Three layers working together. The first is the lift then pull mechanism, two deliberate successive movements that do not happen by a touch or a passing brush. The second is the break glass rod, which adds a physical barrier and leaves a visible trace of any operation. The third is a distinct colour and legend that make the item visually impossible to confuse with the other stations on site.

Q3: Can it be operated without the break-glass rod?

  • Yes. The station works with or without a glass rod according to site policy: the rod is used where preventing an accidental discharge is the priority, and omitted where faster access matters more. Replacing it requires no special tools, so the station returns to service as soon as the event is over without waiting for a specialist technician — and keeping spare rods in site stock is recommended.

Q4: Does the 10 A at 120 VAC rating suit our system?

  • The rating given is the maximum contact capacity, not a required operating voltage. The station is a dry contact of the SPST type that opens or closes an electrical path, and the circuit voltage and current are set by the connected control panel. What is required at design stage is matching the contact type (SPST) to the manual release input at the panel, and our technical team is glad to review the drawing with you before supply.

Q5: Do you deliver to Riyadh, Dammam and all regions of the Kingdom?

  • Yes — supply is available to every region of the Kingdom, Riyadh, Dammam, Jeddah, Jubail, Yanbu and all other regions, within 2-3 business days. On contractor orders the B2B team reviews the bill of quantities, confirms that both the release and the abort station are listed for each protected zone, and prepares the project file and the Civil Defense file.

Internal Links

_________________________________________________________________________________________

Copyright © 2026 — (Al-Najma Al-Wataniyah Est.) — All Rights Reserved — Kingdom of Saudi Arabia We are committed to providing the highest quality standards to our customers in the Kingdom of Saudi Arabia, supplying approved certificates or technical data sheets for every product to ensure your project requirements are met.

Read more
SKU : RE-716P1TLP(G)

253

VAT included
Weight 500 G

Drag & drop file

Browse

Secure Shopping, Your Data is Always Protected

Overview

  • Every gas suppression system has three manual stations in three different colours, and each colour does a job the others do not: red to raise the alarm, yellow to abort or delay the discharge, and green — this item — to start the discharge by hand. The Ravel RE-716P1TLP(G) is the button an operator reaches for on seeing the fire itself, rather than waiting for the automatic detection sequence to complete, and it initiates the discharge of gas or clean agent through the connected control panel. Because operating it leads to a real discharge, it is built around a dual-action lift then pull movement that no passing touch or accidental brush can carry out, and it can be reinforced with a break glass rod that makes operation a deliberate act and leaves a visible trace of any use — or left without one where faster access matters more, with replacement of the rod requiring no special tools so the station is back in service straight away. This is also a device that may sit untouched for years and then be required to work first time, which is the lens to read its construction through: the enclosure is non-toxic die-cast alloy with smooth edges and a low profile that does not obstruct movement in a corridor, behind it sits a black 14 Ga steel plate that takes the strain of wall fixing, and every component is either prepainted or carries a treated surface so that slow corrosion over the years does not become the reason for failure at the decisive moment — a real consideration in Eastern Province humidity and industrial site conditions. The cover is secured by a hex screw or a key lock, so the enclosure opens only to an authorised hand. On the wiring side the station is not a source of voltage but a dry contact: a snap action SPST switch that opens or closes a path, and its rating of 10 amps at 120 VAC is the ceiling of its capacity, not a condition of its use, while the circuit voltage and current come from the control panel to which the station is wired through a two-position terminal block on a standard single-gang box. The compatible Ravel panels are the RE-120GR for gas release and the RE-25AR for agent release. The station is UL Listed — Signaling, it weighs 15.5 oz, and its origin is India. Available from Al-Najma Al-Wataniyah Est. with a quality guarantee and fast supply to projects across the Kingdom in Riyadh, Dammam and all regions.

Technical Specifications

SpecificationValue
CategoryFire Alarm & Gas Release Systems — Manual Release Station
BrandRavel
ModelRE-716P1TLP(G)
FunctionManually initiating the discharge of gas or clean agent
Operating MechanismDual action — lift then pull
Break Glass RodAvailable — the station works with or without it, and replacement requires no special tools
HousingPainted non-toxic die-cast alloy, low-profile design with smooth edges
Back Plate14 Ga plated steel, black
Surface TreatmentAll components prepainted or with plated surfaces to inhibit corrosion
AccessHex screw or key lock
SwitchSnap action, SPST
Electrical Rating10 A at 120 VAC (maximum contact capacity)
Terminal BlockTwo position
MountingSingle gang
Width3.200 in (approx. 81 mm)
Length4.750 in (approx. 121 mm)
Depth0.875 in (approx. 22 mm)
Weight15.5 oz
ColourGreen
CertificationUL Listed — Signaling
Compatible PanelsRE-120GR (conventional gas release panel) · RE-25AR (conventional agent release panel)
Country of ManufactureIndia
SKURE-716P1TLP(G)

Size & Color Table

Article CodeColourSize
RE-716P1TLP(G)GreenSingle model — single-gang mounting

Documentation & Standards

  • This station is UL Listed under the Signaling category for signalling devices in fire systems. The table below translates each line of its specification into practical terms, to support matching it against the panel drawing before purchase:
  • Additional reference standards for the Saudi market:
  • NFPA 2001 (Clean Agent Fire Extinguishing Systems — and the reference for manual actuation requirements within them)
  • NFPA 72 (National Fire Alarm and Signaling Code — the reference for the design and installation of manual actuation devices)
  • UL 38 (the American standard for manually actuated signaling boxes)
  • Saudi Civil Defence (the authority for approving gas suppression systems and their accessories in the Kingdom)
ItemWhat It Means in Practice
UL Listed — SignalingUnderwriters Laboratories listing under the signalling device category, which is what project specifications and approval files require of fire system devices
SPST switchSingle pole, single throw — one contact changes state on operation, matched against the manual release input at the panel
10 A at 120 VACThe maximum contact capacity — the station works as a dry contact whose operating voltage is set by the connected system
Snap action switchA decisive rather than gradual transfer between the two states, so no chattering signal arises on a slow pull — which matters directly on an item that initiates a discharge
Lift then pull mechanismTwo deliberate successive movements that prevent a discharge being started by a single accidental touch
Break glass rodAn optional physical barrier that makes operation a deliberate act and leaves a visible trace of any use

Industrial Applications

  • B2B sectors — detailed engineering use:
Sector / ApplicationEngineering Use Detail
Clean agent suppression systemsThe item that allows discharge to be started by hand on sight of fire, without waiting for the automatic detection sequence to complete
High-value goods warehousesLocations where the difference of seconds between starting the discharge and waiting for detection is a difference in the size of the loss
Server rooms and data centresEnclosed environments staffed by technicians familiar with the system who are able to take the discharge decision themselves
Transformer and main switchboard roomsLocations with a high heat load where a visible manual means of initiation is preferred
Coastal and industrial facilities in the KingdomPrepainted components and corrosion-inhibited surfaces suit humid and salt-laden conditions
Refurbishment and device replacement projectsMounting on a standard single-gang box makes replacement in an existing installation straightforward

Supply Information

FieldValue
Lead Time2-3 Business Days
CoverageRiyadh · Dammam · Jeddah · Jubail · Yanbu · and all regions
Project SupplyAvailable — contact the sales team to price the release and abort stations together and review the bill of quantities against the control panels

Frequently Asked Questions

Q1: What is the difference between the green, yellow and red stations?

  • Three functions in three colours: red is an alarm initiating device, yellow is the station that aborts or delays the discharge, and green — this item — is the station that starts the discharge by hand. A complete system needs the green and the yellow together: one to begin the discharge and one to stop it. The item is always matched against the system drawing and its bill of quantities before purchase.

Q2: What prevents it being operated by mistake?

  • Three layers working together. The first is the lift then pull mechanism, two deliberate successive movements that do not happen by a touch or a passing brush. The second is the break glass rod, which adds a physical barrier and leaves a visible trace of any operation. The third is a distinct colour and legend that make the item visually impossible to confuse with the other stations on site.

Q3: Can it be operated without the break-glass rod?

  • Yes. The station works with or without a glass rod according to site policy: the rod is used where preventing an accidental discharge is the priority, and omitted where faster access matters more. Replacing it requires no special tools, so the station returns to service as soon as the event is over without waiting for a specialist technician — and keeping spare rods in site stock is recommended.

Q4: Does the 10 A at 120 VAC rating suit our system?

  • The rating given is the maximum contact capacity, not a required operating voltage. The station is a dry contact of the SPST type that opens or closes an electrical path, and the circuit voltage and current are set by the connected control panel. What is required at design stage is matching the contact type (SPST) to the manual release input at the panel, and our technical team is glad to review the drawing with you before supply.

Q5: Do you deliver to Riyadh, Dammam and all regions of the Kingdom?

  • Yes — supply is available to every region of the Kingdom, Riyadh, Dammam, Jeddah, Jubail, Yanbu and all other regions, within 2-3 business days. On contractor orders the B2B team reviews the bill of quantities, confirms that both the release and the abort station are listed for each protected zone, and prepares the project file and the Civil Defense file.

Internal Links

_________________________________________________________________________________________

Copyright © 2026 — (Al-Najma Al-Wataniyah Est.) — All Rights Reserved — Kingdom of Saudi Arabia We are committed to providing the highest quality standards to our customers in the Kingdom of Saudi Arabia, supplying approved certificates or technical data sheets for every product to ensure your project requirements are met.